1. HOME
  2. About CC-Link
  3. CC-Link
  4. Specification table of CC-Link V1.10/V2

About the CC-Link Family of Networks

Specification table of CC-Link V1.10/V2

If the entire system consists of V1.10/V2 devices, this provides benefits as follows:

  • 1.The shortest inter-station cable length is 20 cm under all conditions. (when using cable Version 1.10)
  • 2.Flexibility of cable length reduces work when wiring devices.
  • 3.When devices are mounted adjacent to one another, there is no extra cable required, therefore you can use space more efficiently
  • 4.Different brand cables can be used within a single system. If a system uses device stations compatible with Version 1.00, 1.10 and 2.00, and cables compatible with cable Version 1.00 and 1.10, then follow the cable Version 1.00 specification for maximum overall cable extension length and inter-station cable length.
Items Specifications
Version 1.10 Version 2.00 (V2)
Control specifications Maximum
number of
link points
Remote I/O
(RX, RY)
2048
points
each
8192 points each
Remote
register
(RWr)
256
words
2048 words
(Slave station to Master station)
Remote
register
(RWw)
256
words
2048 words
(Master station to Slave station)
Extended cyclic setting - 1 time
setting
2 time
setting
4 time
setting
8 time
setting
Number
of link
points per
unit
1
station
occupied
RX, RY 32 points each
32
points
each
64
points
each
128
points
each
RWr,RWw 4 words 8
words each
16
words each
32
words each
2
stations
occupied
RX, RY 64 points each 96
points
each
192
points
each
384
points
each
RWr,RWw 8 words 16
words each
32
words each
64
words each
3
stations
occupied
RX, RY 96 points each 160
points
each
320
points
each
640
points
each
RWr,RWw 12 words 24
words each
48
words each
96
words each
4
stations
occupied
RX, RY 128 points each 224
points
each

448
points
each

896
points
each

RWr,RWw 16 words 32
words each
64
words each
128
words each
Maximum number of
occupied stations
4 stations
Communication specification Communication speed 10M / 5M / 2.5M / 625k / 156kbps
Communication system Broadcast polling system
Synchronization system Frame synchronization system
Encoding system NRZI
Transmission path format Bus format (EIA RS485 conformance)
Transmission format HDLC conformance
Error control system CRC (X16+X12+X5+1)
Max. number of units connected 64 units
The number of slave station 1 - 64
Max. overall cable extension length and inter-station cable length

CC-Link Ver 1.10 compatible cable (Using 110Ω terminators)

squareCC-Link cable Version 1.10 (Using 110Ω terminators)
Communication
speed
Inter-station cable
length
Max. overall cable
extension length
156kbps 20 cm or longer 1200m
625kbps 900m
2.5Mbps 400m
5Mbps 160m
10Mbps 100m

If a system uses device stations compatible with Version 1.00, 1.10 and 2.00, and cables compatible with cable Version 1.00 and 1.10, then follow the cable Version 1.00 specification for maximum overall cable extension length and inter-station cable length.

Connection cable

CC-Link cable Version 1.10
(Shielded, 3-core twisted pair cable)

* Mixture of different brand cables is possible only when they are all CC-Link cable Version 1.10 compatible cables.

CC-Link Ver. 1.00 model (Differences from Ver. 1.10)

There are two differences in specifications between CC-Link Ver. 1.10 and Ver. 1.00 as shown below.

  • Max. overall cable extension length and inter-station cable length
  • Connection cable
Items Specifications
Max. overall cable
extension length and
inter-station cable length

Specifications

  • *1:Inter-station cable length between remote I/O or remote device stations
  • *2:Inter-station cable length between the master station and a local station or between an intelligent device station and the preceding or following station
squareCC-Link Ver 1.10 compatible cable (Using 110Ω terminators)
Communication speed Inter-station cable length Max. overall cable extension length
*1 *2
156Kbps 30cm or over 1m or over (A)
/
2m or over (B)
1200m
625Kbps 600m
2.5Mbps 200m
5Mbps 30cm to 59cm* 110m
60cm or over 150m
10Mbps 30cm to 59cm* 50m
80m
1m or over 100m
  • (A):1m or longer: In the case of a system comprising only remote I/O or remote device stations
  • (B):2m or longer: In the case of a system comprising local and intelligent device stations
  • *If even a cable between remote I/O or remote device stations is to be wired within this range, the maximum overall cable length shown above applies.
Connection cable

CC-Link Ver. 1.10 compatible cable (Shielded, 3-core twisted pair cable)
* Cables of different manufacturers cannot be used together.

How to distinguish cables

Regarding the logo placement, please contact the manufacturer for the CC-Link cable Version 1.10 product.

squareCable Identification

How to distinguish cables

CC-Link Family of Networks

  • CC-Link IE
    • CC-Link IE TSN
    • CC-Link IE Field
      • CC-Link IE Field Basic
      • CC-Link IE Field Motion
    • CC-Link IE Control
    • CC-Link IE Safety
  • SLMP
  • CC-Link
    • CC-Link Configuration
    • CC-Link version description
    • What is CC-Link Ver. 2.00?
    • V1.10 / V2
    • T branch
    • CC-Link Safety
    • CC-Link/LT
  • CSP+
  • CSP+ for Machine
  • News & Events
    News & Events
  • Downloads
    Downloads
  • Contact
    Contact
CC-Link Partner
Association (CLPA)
Members Site
CC-Link CLPA

Loginnew window

Page Top